Environment-Friendly Gas-Insulated Ring Network Switchgear
The HBXGN-24 environment-friendly gas-insulated ring network switchgear employs a vacuum arc-extinguishing chamberutilizes eco-friendly gas as the primary insulation medium with minor solid insulation supports, and features no encapsulation in themain circuit. lt operates at zero gauge pressure or sightly positive pressure (with the gas tanks air pressure not exceeding0.02MPa) during normal conditions, and its insulation capablities relative to ground and between phases satisfy the air insulatiorrequirements at zero gauge pressure. This environment-friendly gas-insulated ring network switchgear is a frequently employed three-phase Ac inteligent cabinetextensively utilized in various switchgear assemblies, As the population becomes more concentrated domestically, the powermarket must adapt accordingly, necessitating a growing demand for eco-friendly gas-insulated switchgear alongside marketdevelopment; The market's potential remains untapped. Additionally, with features that integrate data acquisition and control, dataprocessing and storage, and online monitoring and advanced analysis of switchgear, this product inteligently conducts onlinemonitoring and management ot distnbution networks, ensuring they operate in a sate, relable, high-guality. and eticient mannerIt faciitates remote monitoring, control, and management of power system distribution networks, fulfiling the requirements forpower grid optimization, electrical safety, energy management, and the reduction of energy consumption and waste. furthermorethe system is broadly applicable in inteligent power distribution sectors, including transportation, factories, hospitals, schoolsbuildings,residential complexes, and commercial office buildings.
Maximum temperature: +40℃Minimum temperature: -25℃ 24-hour average temperature: s35℃ Maximum average relative humidity: 24-hour average s 95%, monthly average s 90% Altitude: s 1500 meters (conventional type, under standard inflation pressure),>1500 meters requires special instructions. For special operating conditions beyond normal use environment, please consult with our company in advance.
Item
Module C
Module F
Module V
Load switch
Assembled electrical apparatus
Vacuum circuitbreaker
Isolation/grounding switches
Rated Voltage
40.5
Power-frequency withstand voltage for 1 minute
42/48
Lightning impulse withstand voltage
75/85
Rated current
630
125*
630
630
Breaking capacity
Closed-loop breaking current
630
Cable charging breaking current
135
5% active load breaking current
31.5
Ground fault breaking current
200
Short-circuit breaking current
31.5*
25
25
Rated transfer current
1500
Select the maximum current of the fuse
125
Short-circuit closing current
63
80*
25
Short-time withstand current
25
25
25
Short-circuit duration
4
4
4
Mechanical Life
5000
5000
10000
3000
Gas pressure
0.025 (20℃)
Annual leakage rate
≤0.05%
Arc extinguishing method
Vacuum quenching
Protection grade
IP67/3X (gas tank/housing)
1-way
2-way
3-way
4-way
5-way
W(mm)
420
696
1021
1346
1671
H(mm)
1336
D(mm)
850(total 935)